How to adjust the tunnel fan to the best status?
Tunnel ventilation fan is
currently one of the most widely used ventilation and exhaust equipment in
industrial production, but due to the influence of professional knowledge, many
business owners often ignore it once it is installed. In fact, under different
conditions of the tunnel fan, the effect can be different. Therefore, how to
debug so that the tunnel fan can be in the best state is very important.
1. The fan allows full-voltage starting or
step-down electric, but it should be noted that the current at full-voltage
starting is about 5-7 times the rated current, and the step-down starting
torque is proportional to the voltage square. When the grid capacity is
insufficient, the fan should be Start with reduced voltage.
2. When the tunnel fan is commissioned,
carefully read the product manual and check whether the wiring method is
consistent with the wiring diagram; carefully check whether the working voltage
of the power supply to the fan meets the requirements, whether the power supply
is out of phase or in the same phase, Whether the capacity meets the
requirements.
3. During the test run, there should be no
less than two people. One person controls the power supply, and one person
observes the operation of the fan. If any abnormality is found, the machine
will immediately stop and check. First, check whether the rotation direction is
correct. Whether the current exceeds the rated current; if there is any
abnormal phenomenon, stop and check. After running for five minutes, stop the
fan to check whether there is any abnormal phenomenon, and confirm that there
is no abnormal phenomenon before turning on the machine.
4. When testing a two-speed fan, start it
at a low speed and check whether the direction of rotation is correct. When
starting at a high speed, you must wait for the fan to stop before starting to
prevent high-speed reverse rotation, causing switch tripping and motor damage.
Share from Boxing Motexo Industries Co.,Ltd.
5. When the fan reaches normal speed, it
should be measured whether the fan input current is normal, and the running
current of the tunnel fan cannot exceed its rated current. If the operating
current exceeds its rated current, check whether the supplied voltage is
normal.